Component Replacement Procedures Chapter 3

3. Install the four screws that hold the Fan and cover together.

4. Place Fan unit in position, locating Fan

wire in bottom left corner.

5. Install the 12 screws at the exterior of

fan cover.

6. Reconnect Fan wire.

7. Reassemble remaining components in reverse order.

8. Replace all safety shields and enclosure covers before applying power to

the drive.

Fan Transformer

Refer to the figures in

Component Diagrams and Torque Specs on page 13

for

these instructions.

Remove Components

1. Read and follow the

Safety Precautions on page 9

and

Important Initial

Steps on page 11

.

2. Perform

Remove Precharge Board Assembly on page 23

.

3. Label and unscrew or disconnect wires for the Transformer.

4. Unscrew Transformer mounting brackets.

Install Components

1. Install new Transformer by screwing mounting brackets to drive.

2. Reconnect all wires and connectors for the Transformer.

3. Reassemble remaining components in reverse order.

4. Replace all safety shields and enclosure covers before applying power to

the drive.

Current Transducer

Refer to the figures in

Component Diagrams and Torque Specs on page 13

for

these instructions.

Remove Components

1. Read and follow the

Safety Precautions on page 9

and

Important Initial

Steps on page 11

.

2. Remove the safety cover.

TIP

When replacing Motor Bus Bars, remove nearby terminal
block barriers to provide additional maneuvering space.