PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Running an Assisted Start Up

The Assisted start-up routine prompts you to input required information. Access
Assisted Start Up by selecting “Start Up” from the Main Menu.

To perform an Assisted Start-Up

Drive Status Indicators

IMPORTANT

This start-up routine requires an LCD HIM.

Step

Key(s)

Example LCD Displays

1. In the Main Menu, press the Up Arrow or

Down Arrow to scroll to “Start Up”.

2. Press Enter.

IMPORTANT

Done/Exit must be selected upon completion of the Start Up routine in order
for any Start Up/Autotune data to be saved.

Name

Color

State

Description

Green

Steady

Illuminates when power is applied to the drive.

Green

Flashing

Drive ready, but not running and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing, Drive
Stopped

An inhibit condition exists, the drive cannot be started. Check
parameter 214 [Start Inhibits].

Flashing, Drive
Running

An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].

Steady,
Drive Running

A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].

Red

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Refer to the Communication
Adapter User Manual.

Status of DPI port internal communications (if present).

Status of communications module (when installed).

Status of network (if connected).

Status of secondary network (if connected).

F-> Stopped

Auto

0.0

Hz

Main Menu:

Memory Storage

Start Up

Preferences

POWER

STS

PORT

MOD

NET A

NET B