Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

65

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Supplemental Information

Using PowerFlex Drives w/Regen Units

If a Regenerative unit (for example, 1336 REGEN) is used as a bus supply or
brake, the common mode capacitors must be disconnected as described on

page 43

.

Connections to the 1336 REGEN

Regen Brake Mode

Regenerative Bus Supply Mode

DC Input (Common Bus) and Precharge Notes

The following notes must be read and understood. Also refer to pages

26

through

30

for additional DC input information.

Important Application Notes

1.

If drives without internal precharge are used (Frames 5 & 6 only), then:
a. precharge capability must be provided in the system to guard against

possible damage, and

b. disconnect switches Must Not be used between the input of the drive

and a common DC bus without the use of an external precharge device.

2.

If drives with internal precharge (Frames 0…6) are used with a disconnect
switch to the common bus, then:
a. an auxiliary contact on the disconnect must be connected to a digital

input of the drive. The corresponding input (parameter 361…366)
must be set to “30, Precharge Enable.” This provides the proper
precharge interlock, guarding against possible damage to the drive
when connected to a common DC bus.

b. the drive must have firmware version 2.002 or above.

Frame(s)

Terminals

1336 REGEN

PowerFlex 700

0…4

DC+

BR1

DC–

DC–

5…6

DC+

DC+

DC–

DC–

Frame(s)

Terminals

1336 REGEN

PowerFlex 700

0…4

DC+

DC+

DC–

DC–

5…6

DC+

DC+ of Common Bus Drives

DC–

DC– of Common Bus Drives