PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Terminal Block Details
Frame
Power Terminal Blocks
0…1
Notes:
Shaded BR1 & BR2 Terminals are only present on
drives ordered with the Brake Option.
➊Precharge Resistor Fuse – DCT12-2
(DC input drives w/precharge only)
➋M8 Stud (All Terminals)
Max. Lug Width = 25.4 mm (1 in.)
➌M8 Stud (All Terminals)
Max. Lug Width = 31.8 mm (1.25 in.)
2
3…4
AC Input (Ratings are Normal Duty)
DC Input (Ratings are Normal Duty)
5
240V, 40 Hp
480V, 75 Hp
690V, 45…90 kW
400V, 55 kW
600V, 75 Hp
240V, 40 Hp
480V, 75 Hp
690V, 45…90 kW
400V, 55 kW
600V, 75 Hp
240V, 50 Hp
480V, 100 Hp
400V, 75 kW
600V, 100 Hp
240V, 50 Hp
480V, 100 Hp
400V, 75 kW
600V, 100 Hp
6
125…200 Hp
125…200 Hp
BR1
BR2
DC+
DC–
PE
U (T1)
V (T2)
W (T3)
R (L1)
S (L2)
T (L3)
T
(L3)
S
(L2)
R
(L1)
W
(T3)
V
(T2)
U
(T1)
PE
DC–
DC+
BR2
BR1
T
(L3)
S
(L2)
R
(L1)
W
(T3)
V
(T2)
U
(T1)
DC–
DC+
BR2
BR1
T/L3
S/L2
R/L1
PE
PE
W/T3
V/T2
U/T1
DC–
DC+
BR1*/
DC+
BR2*
PS–
PS+
240
VAC
120
VAC
0
VAC
PE
PE
W/T3
V/T2
U/T1
DC–
DC+
BR1*/
DC+
BR2*
PS–
PS+
➊
T/L3
S/L2
R/L1
PE
PE
W/T3
V/T2
U/T1
DC–
DC+
BR1*/
DC+
BR2*
PS–
PS+
240
VAC
120
VAC
0
VAC
PE
PE
W/T3
V/T2
U/T1
DC–
DC+
BR1*/
DC+
BR2*
PS–
PS+
➊
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
DC–
DC+
BR1
BR2
V
T2
W
T3
R
L1
S
L2
INPUT
OUTPUT
T
L3
PE
PE
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
➌
DC–
DC+
BR1
BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS–
U
T1
V
T2
W
T3
PE
PE
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
OUTPUT
22-10 AWG
5.3 IN-LB
(0.6 N-M)
FA
N
INPUT
1-PHASE
0 V
A
C
120 V
A
C
240 V
A
C
➊
➋