Do not remove mov – Rockwell Automation 20B PowerFlex 700 Installation Instructions - Frames 0…6 User Manual
Page 50
50
Rockwell Automation Publication 20B-IN019E-EN-P - July 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6
Fram
e
Vo
lt
ag
e
Code
Current
Ra
ti
ng
Factory Default Jumper Settings
Power Source Type
MOV/Input
Filter Caps
(1) (2)
DC Bus Common
Mode Caps
6
IP20, NEMA/UL Type 1 and Open Drives
B
C
D
H
J
N
P
R
All
Two green/yellow
wires connected
to Power Terminal
Block “PE”
Green/yellow wire to
CM Cap Board is
connected to Power
Terminal Block “PE”
Solid Ground
1. The green/yellow CM Cap jumper wire must be
connected to “PE.”
2. The MOV/Input Filter Cap jumper wires must
be connected to “PE.”
Non-Solid Ground
1. The green/yellow CM Cap jumper wire must be
insulated from ground. Verify, and if necessary,
remove the jumper wire from “PE” and
insulate/secure it to guard against
unintentional contact with chassis or
components. Important: Do Not Remove/
Disconnect the larger green/yellow wire.
2. MOV/Input Filter Cap jumper wires must be
insulated from ground. Verify, and if necessary,
remove the jumper wires from “PE” and
individually insulate/secure each jumper wire
to guard against unintentional contact with
chassis or components.
Frame 6 continued on next page
(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2) When removing MOV’s, the input filter capacitor must also be removed.
DC–
DC+
BR1
BR2
USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)
22-10
AWG
5.3 IN-LB
(0.6 N-M)
WIRE STRIP
PS+
PS
–
USE 75 C
COPPER WIRE
ONLY
TORQUE
52 IN-LB
(6 N-M)
U
T1
V
T2
W
T3
R
L1
S
L2
INPUT
OUTPUT
T
L3
PE
PE
Optional
Communications
Module
PE
PE
MOV
Input Filter Cap
CM Cap
DO NOT
REMOVE
MOV