beautypg.com

Rockwell Automation 20B PowerFlex 700 Installation Instructions - Frames 0…6 User Manual

Page 49

background image

Rockwell Automation Publication 20B-IN019E-EN-P - July 2013

49

PowerFlex 700 Adjustable Frequency AC Drive – Frames 0…6

Fram

e

Vo

lt

ag

e

Code

Current

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input
Filter Caps

(1) (2)

DC Bus Common
Mode Caps

5

IP54, NEMA Type 12 Drives (continued)

E
F
T

W

All

Two green/yellow
wires connected
to chassis ground

Green/yellow wire to
CM Cap Board is
connected to ground

Solid Ground

1. CM Cap jumper wire must be connected to

ground with a metal screw. Verify, and if
necessary, remove the nylon screw/spacer and
insert a metal M5 x 12 screw. Torque to 3.2
N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires must be

connected to ground with a metal screw.
Verify, and if necessary, remove the nylon
screw/spacer and insert a metal M5 x 12
screw.

Non-Solid Ground

1. CM Cap jumper wire must be insulated from

ground with a nylon screw/spacer. Verify, and
if necessary, remove the metal screw and
insert a M5 x 20 nylon screw/spacer.

2. MOV/Input Filter Cap jumper wires must be

insulated from ground with a nylon screw/
spacer. Verify, and if necessary, remove the
metal screw and insert a M5 x 20 nylon screw/
spacer.

(1) AC input drives only. MOV’s and input filter caps do not exist on DC input drives.

(2) When removing MOV’s, the input filter capacitor must also be removed.

USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)

POWER & DC TERMINAL RATINGS

WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)

BRAKE TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (18-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

OUTPUT

INPUT AC

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

DANGER

DANGER

RISK OF ELECTRIC
SHOCK AND DEATH

FIELD INSTALLED OPTIONS

6 MM HEX KEY

6 MM HEX KEY

SHLD

SHLD

CM Cap

MOV

MOV / Input Filter Cap