beautypg.com

Psw2, Ovrd – Titus Sensor STE-8001 and STE-8201 User Manual

Page 32

background image

KMC Controls

Revision A

Commissioning functions
Advanced options

32

Enter a new
Level 2 password
password

Note:

Entering four zeros (0000) removes

the password.

1. Press the or buttons to change

the first digit.

2. Press the button to select the next

digit. Repeat for all four digits.

3. When the button is pressed for the

last digit, the new password is saved
and the display advances.

Set the local
unoccupied
override timer

Note:

This function applies only to

controllers that will use an STE-6017
sensor.

1. Press the or buttons to set the

local unoccupied override timer. The
value will change in 1 minute
increments.

2. Press the button to save the

setpoint and advance to the next
function.

Set the standby
time

Note:

This function applies only to

controllers that will use an STE-8201
sensor.

3. Press the or buttons to set the

time for the standby time. The value
will change in 1 minute increments.

4. Press the button to save the

setpoint and advance to the next
function.

Set discharge air
temperature
limiting

1. Press the or buttons to enable or

disable discharge air temperature
limiting.

2. Press the button to save the

setpoint and advance to the next
function.

Set the STE-8000
temperature sensor
calibration
constant

1. Press the or buttons to set the

calibration constant. The setpoint
will change in 0.1 minute increments.

2. Press the button to save the

setpoint and advance to the next
function.

Procedure to set the advanced options (Continued)

Procedure

Steps

STE display

Set

Point

Set

Point

PSW2

OOOO

Set

Point

3O

OVRD

Set

Point

15

Set

Point

DISABLE

DAT

Set

Point

OO

CALIB