Psw2, Ovrd – Titus Sensor STE-8001 and STE-8201 User Manual
Page 32
KMC Controls
Revision A
Commissioning functions
Advanced options
32
Enter a new
Level 2 password
password
Note:
Entering four zeros (0000) removes
the password.
1. Press the or buttons to change
the first digit.
2. Press the button to select the next
digit. Repeat for all four digits.
3. When the button is pressed for the
last digit, the new password is saved
and the display advances.
Set the local
unoccupied
override timer
Note:
This function applies only to
controllers that will use an STE-6017
sensor.
1. Press the or buttons to set the
local unoccupied override timer. The
value will change in 1 minute
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the standby
time
Note:
This function applies only to
controllers that will use an STE-8201
sensor.
3. Press the or buttons to set the
time for the standby time. The value
will change in 1 minute increments.
4. Press the button to save the
setpoint and advance to the next
function.
Set discharge air
temperature
limiting
1. Press the or buttons to enable or
disable discharge air temperature
limiting.
2. Press the button to save the
setpoint and advance to the next
function.
Set the STE-8000
temperature sensor
calibration
constant
1. Press the or buttons to set the
calibration constant. The setpoint
will change in 0.1 minute increments.
2. Press the button to save the
setpoint and advance to the next
function.
Procedure to set the advanced options (Continued)
Procedure
Steps
STE display
Set
Point
Set
Point
PSW2
OOOO
Set
Point
3O
OVRD
Set
Point
15
Set
Point
DISABLE
DAT
Set
Point
OO
CALIB