Setting up network communications, Psw2, Comm – Titus Sensor STE-8001 and STE-8201 User Manual
Page 15: D id, Baud
![background image](/manuals/574449/15/background.png)
STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Setting up network communications
15
Setting up
network
communications
Set the network communication settings before placing a controller on the
network. Setting network settings requires entering the Level 2 password which
is described in the topic
Enter the commissioning mode on page 14
Procedure to set up network communications
Procedure
Steps
STE display
Starting display
1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the COMM.
Select the COMM
display
Press the button. The display changes
to DI D.
Enter the device
instance.
1. Press the or buttons to change
the first digit.
2. Press the button to select the next
digit. Repeat for all seven digits.
3. When the button is pressed for the
last digit, the display changes to MAC.
Enter the MAC
address.
1. Press the or buttons to change
the MAC address.
2. Press the button to save the
selected MAC address.
The display changes to BAUD.
Enter the baud
1. Press the or buttons to select a
new baud.
2. Press the button is save the
selected baud.
The display returns to COMM.
Advance or exit
1. Press the or buttons to select
one of the following:
•
BLNC
or
CNFG
options
•
EXIT
to return to the temperature
display.
2. Press the button to select the next
function.
72
12S1
PSW2
OOOO
Set
Point
COMM
Set
Point
Set
Point
D ID
OO72O69
Set
Point
MAC
11
Set
Point
BAUD
384OO
Set
Point
COMM