Titus Fan Powered Term. IOM User Manual
Fan powered terminals vav terminals, Receiving inspection, Supporting the assembly
Discharge
Air
Flow
Hanger Rod
1 1/2"
1 1/2"
Optional
Hanger
Bracket
Access Panel
(Entire Bottom is
Removeable)
Straps
D
Air
Flow
Discharge
TU-FB-IOM 08-26-13
Fan Powered Terminals VAV Terminals
Receiving Inspection
After unpacking the terminal, check it for
shipping damage. If any shipping
damage is found, report it immediately
to the delivering carrier. Store units in a
clean dry location and do not stack more
than four high.
Caution: Do not use the inlet collar,
damper shaft, flow sensor or air
tubing as a handle to lift or move
assembly. Damage to the unit or
controls may result.
Before installation, remove fan packing
and all foreign material from the unit.
Check the blower wheel for free rotation.
Supporting the Assembly
Suspend the unit from the building
structure in a horizontal plane with the
access panels facing downward.
Do not obstruct the access panels
with support channels or straps.
One inch long sheet metal screws can
be used to penetrate the casing (see
Figure 1). Use the support method
prescribed for the rectangular duct on
the job specifications. Unit may be
equipped with optional hanging brackets
(see Figure 2). Hanger rod up to 7/16"
diameter may be used.
Note: If equipped with pneumatic
controls, or unit is parallel fan type
(Model TQP or FLP), the terminal must
be mounted right side up. It must be
level within ±10 degrees of horizontal,
both parallel to the air flow and at the
right angle of air flow. The control side of
the terminal is labeled with an arrow
indicating UP.
Duct Connections
Slip each inlet duct over the inlet collar
of the terminal. Fasten and seal the
connection by the method prescribed by
the job specification.
The diameter of the inlet duct “D” in
inches must be equal to the listed size of
the terminal; e.g. a duct that actually
measures 8 inches must be fitted to a
size 8 terminal. The inlet collar of the
terminal is made 1/8" smaller than listed
size in order to fit inside the duct (see
Figure 1).
Important: Do not insert duct work
inside the inlet collar of the
assembly.
Inlet duct should be installed in
accordance with SMACNA guidelines.
Rectangular discharge opening is
designed for flanged duct connections.
Fasten and seal by method prescribed
in the job specification.
If single-point electronic velocity sensor
is used, 3 to 5 inlet duct diameters of
straight duct should be provided at the
terminal inlet.
Minimum Access
Fan Powered terminals require sufficient
clearance to service the fan blower
assembly and internal actuator (if so
equipped) from the bottom of the unit,
low voltage controls from the side of the
unit, and line voltage motor controls or
electric heat section (if so equipped)
from the rear or discharge of the unit.
For bottom access panel removal, 3"
minimum vertical clearance below the
unit is required, plus sufficient horizontal
clearance to slide the access panel clear
of the bottom of the unit. Horizontal
clearance is dependent on access panel
dimensions as indicated on product
submittals.
For low voltage control enclosure
access, a minimum of 18" is
recommended.
Specific
control
enclosure location is indicated on
product submittals. Panel for low voltage
enclosures are removable (not hinged).
For line voltage motor controls or electric
heat control access, a minimum of 36"
should be provided to allow full opening
of hinged access doors. Specific location
is indicated on product submittals.
Important: These recommendations
do not preclude NEC or local codes
that may be applicable, which are
the responsibility of the installing
contractor.
Figure 1.
Figure 2.
1 of 9
This IOM is meant to demonstrate general product details. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to
make changes without written notice.
All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air
Distribution Technologies.