beautypg.com

Titus Fan Powered Term. IOM User Manual

Fan powered terminals vav terminals, Receiving inspection, Supporting the assembly

background image

Discharge

Air

Flow

Hanger Rod

1 1/2"

1 1/2"

Optional

Hanger

Bracket

Access Panel

(Entire Bottom is

Removeable)

Straps

D

Air

Flow

Discharge

TU-FB-IOM 08-26-13

Fan Powered Terminals VAV Terminals

Receiving Inspection

After unpacking the terminal, check it for

shipping damage. If any shipping

damage is found, report it immediately

to the delivering carrier. Store units in a

clean dry location and do not stack more

than four high.

Caution: Do not use the inlet collar,

damper shaft, flow sensor or air

tubing as a handle to lift or move

assembly. Damage to the unit or

controls may result.

Before installation, remove fan packing

and all foreign material from the unit.

Check the blower wheel for free rotation.

Supporting the Assembly

Suspend the unit from the building

structure in a horizontal plane with the

access panels facing downward.

Do not obstruct the access panels

with support channels or straps.

One inch long sheet metal screws can

be used to penetrate the casing (see

Figure 1). Use the support method

prescribed for the rectangular duct on

the job specifications. Unit may be

equipped with optional hanging brackets

(see Figure 2). Hanger rod up to 7/16"

diameter may be used.

Note: If equipped with pneumatic

controls, or unit is parallel fan type

(Model TQP or FLP), the terminal must

be mounted right side up. It must be

level within ±10 degrees of horizontal,

both parallel to the air flow and at the

right angle of air flow. The control side of

the terminal is labeled with an arrow

indicating UP.

Duct Connections

Slip each inlet duct over the inlet collar

of the terminal. Fasten and seal the

connection by the method prescribed by

the job specification.

The diameter of the inlet duct “D” in

inches must be equal to the listed size of

the terminal; e.g. a duct that actually

measures 8 inches must be fitted to a

size 8 terminal. The inlet collar of the

terminal is made 1/8" smaller than listed

size in order to fit inside the duct (see

Figure 1).

Important: Do not insert duct work

inside the inlet collar of the

assembly.

Inlet duct should be installed in

accordance with SMACNA guidelines.

Rectangular discharge opening is

designed for flanged duct connections.

Fasten and seal by method prescribed

in the job specification.

If single-point electronic velocity sensor

is used, 3 to 5 inlet duct diameters of

straight duct should be provided at the

terminal inlet.

Minimum Access

Fan Powered terminals require sufficient

clearance to service the fan blower

assembly and internal actuator (if so

equipped) from the bottom of the unit,

low voltage controls from the side of the

unit, and line voltage motor controls or

electric heat section (if so equipped)

from the rear or discharge of the unit.

For bottom access panel removal, 3"

minimum vertical clearance below the

unit is required, plus sufficient horizontal

clearance to slide the access panel clear

of the bottom of the unit. Horizontal

clearance is dependent on access panel

dimensions as indicated on product

submittals.

For low voltage control enclosure

access, a minimum of 18" is

recommended.

Specific

control

enclosure location is indicated on

product submittals. Panel for low voltage

enclosures are removable (not hinged).

For line voltage motor controls or electric

heat control access, a minimum of 36"

should be provided to allow full opening

of hinged access doors. Specific location

is indicated on product submittals.

Important: These recommendations

do not preclude NEC or local codes

that may be applicable, which are

the responsibility of the installing

contractor.

Figure 1.

Figure 2.

1 of 9

This IOM is meant to demonstrate general product details. The drawings are not meant to detail every aspect of the product. Drawings are not to scale. Titus reserves the right to

make changes without written notice.

All rights reserved. No part of this work may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying and recording, or by any information storage retrieval system without permission in writing from Air

Distribution Technologies.