Setting commissioning setpoints, Psw2, Comm cnfg stpt – Titus Sensor STE-8001 and STE-8201 User Manual
Page 20
![background image](/manuals/574449/20/background.png)
KMC Controls
Revision A
Commissioning functions
Setting commissioning setpoints
20
Setting
commissioning
setpoints
The commissioning setpoints set the operational parameters and limits for the
VAV terminal unit. Setting configuration setpoints requires entering a Level 2
password which is described in the topic
Enter the commissioning mode on
.
Procedure to set the commissioning setpoints
Procedure
Steps
STE display
Starting display
Enter the Level 2 password. The display
changes to the COMM.
Select the setpoint
display.
1. From the COMM display, press the
or buttons to show the CNFG
display.
2. Press the button to select the CNFG
options. The display changes to
STPT.
3. Press the button to select the STPT
options.
Set the minimum
cooling setpoint
1. Press the or buttons to set the
minimum cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the maximum
heating setpoint
1. Press the or buttons to set the
maximum heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
Set
Point
MIN
68O
Set
Point
MAX
78O