Mncl, Mxcl, Mnht – Titus Sensor STE-8001 and STE-8201 User Manual
Page 24: Mxht
KMC Controls
Revision A
Commissioning functions
Setting the airflow setpoints
24
Set the cooling
minimum airflow
limit
1. Press the or buttons to set the
minimum limit for cooling airflow.
The setpoint will change in 1 CFM
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the cooling
maximum airflow
limit
1. Press the or buttons to set the
maximum limit for cooling airflow.
The setpoint will change in 1 CFM
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the heating
minimum airflow
limit
1. Press the or buttons to set the
minimum limit for heating airflow.
The setpoint will change in 1 CFM
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the heating
maximum airflow
limit
1. Press the or buttons to set the
maximum limit for heating airflow.
The setpoint will change in 1 CFM
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the minimum
limit for fan speed
1. Press the or buttons to set the
minimum limit for the fan speed. The
setpoint will change in 1%
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the maximum
limit for fan speed
1. Press the or buttons to set the
maximum limit for the fan speed.
The setpoint will change in 1%
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Procedure to set the airflow setpoints (Continued)
Procedure
Steps
STE display
Set
Point
OO
MNCL
Set
Point
3SO
MXCL
Set
Point
OO
MNHT
Set
Point
3SO
MXHT
Set
Point
2O
MIN
Set
Point
1OO
MAX