Pmax, Pmin – Titus Sensor STE-8001 and STE-8201 User Manual
Page 28
![background image](/manuals/574449/28/background.png)
KMC Controls
Revision A
Commissioning functions
Balancing airflow
28
Measure and enter
the actual
maximum primary
airflow
The display begins flashing PMAX
and also displays the actual airflow
at the bottom.
Note:
The airflow will attempt to stabilize
on the highest value for either the cooling
or heating maximum airflow even if only
one mode is operational.
Note:
The airflow displayed by the
STE-8000 in this step is the actual,
uncorrected airflow.
1. Wait for the maximum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. PMAX stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
changes to PMIN.
Measure and enter
the actual
minimum primary
airflow
The display begins flashing PMIN
and also displays the actual airflow
at the bottom.
Note:
The airflow will attempt to stabilize
on the lowest value for either the cooling
or heating minimum airflow even if only
one mode is operational.
Note:
The airflow displayed by the
STE-8000 in this step is the actual,
uncorrected airflow.
1. Wait for the minimum airflow value
to stabilize.
2. With a flow hood, measure the actual
airflow.
3. Press the button to advance to the
entry display. PMIN stops flashing.
4. Press the or buttons to enter the
measured airflow.
5. Press the button to save the
measured airflow. The display
advances to PRI.
The airflow balancing procedure (Continued)
Procedure
Steps
STE display
Set
Point
Set
Point
PMAX
OO
Set
Point
Set
Point
PMIN
OO