Titus Alpha Commissioning Guide User Manual
Titus Equipment
Alpha Controller
Configuration with STE-8000 Series
1
POWER ON
- The LCD will display the room temperature.
CHANGING SETPOINT - Press SETPOINT once to select COOLING OCCUPIED SETPOINT.
- Press UP/DOWN to change numerical value.
- Press SETPOINT again to select HEATING OCCUPIED SETPOINT.
- Press SETPOINT to return to Room temperature display.
CONTROLLER
- Press and hold both UP & DOWN arrows for 5 seconds to enter into the CONFG MENUS
CONFIGURATION
MENUS
** Refer to the Titus STE-8001 installation guide for additional details **
The Titus APLHA Controller can be programmed in three different ways:
-
Factory Set Up
-
BAS/ Computer thru BACnet network with an additional router.
-
STE- 8000 Series Thermostat (see below)
The Titus STE-8001 series thermostat has (3) buttons:
-
UP / DOWN, and SETPOINT
-
The flow chart on the following pages is intended to simplify the
calibration procedure.
-
Please note that a Level 1 password is required to change the set-point
temperature on the thermostat and a Level 2 password is required for
commissioning.