Revision A

Commissioning functions
The commissioning sequence

14

The
commissioning
sequence

Set the commission functions in the following sequence.

1.

Enter the commissioning mode on page 14

2.

Setting up network communications on page 15

3.

Box options on page 16

4.

Setting commissioning setpoints on page 20

5.

Setting the airflow setpoints on page 23

6.

Balancing airflow on page 27

Enter the
commissioning
mode

For access to the commissioning functions you will need a Level 2 password.

If the controller has not been previously set up, no password is required.

A new Level 2 password can be entered in the advanced commissioning
functions. See the topic

Advanced options

on page 31

.

Enter the commissioning mode

Procedure

Steps

STE display

Starting display

Start from the temperature display.

Enter the
commissioning
password

1. Press the and buttons together

and hold them down until the
display changes to PSW2.

2. Press the or button to change

the first digit.

3. Press the button to select the next

digit. Repeat for all four digits.

4. When the button is pushed for the

fourth correct digit, the display
changes to COMM.

Note:

If a Level 2 password has not

previously been entered the display
will change to the COMM display after
Step 1.

Select a
commissioning
function

Access to the commissioning
functions always start at the COMM
display.

72

12S1

Set

Point

Set

Point

PSW2

OOOO

COMM