Diff, Ddof, Dddp – Titus Sensor STE-8001 and STE-8201 User Manual
Page 22: C2sp, Stpt
![background image](/manuals/574449/22/background.png)
KMC Controls
Revision A
Commissioning functions
Setting commissioning setpoints
22
Set the minimum
temperature
differential
setpoint
1. Press the or buttons to set the
differential setpoint. The setpoint
will change in 1° increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the standby
differential
setpoint
1. Press the or buttons to set the
standby differential setpoint. The
setpoint will change in 1° increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the supply
exhaust offset
1. Press the or buttons to set the
supply exhaust offset setpoint. The
setpoint will change in 1%
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the supply
exhaust differential
pressure setpoint
1. Press the or buttons to set the
supply exhaust differential pressure
setpoint.The setpoint will change in
increments of 0.01 inches of water.
2. Press the button to save the
setpoint and advance to the next
function.
Set the CO2
setpoint.
1. Press the or buttons to change
CO2 setpoint. The setpoint changes
increments for 1 part per million.
2. Press the button to save the
setpoint and complete the setpoint
changes.
The display returns to STPT.
Advance or exit
1. Press the or buttons to select
one of the following:
•
FLOW
,
BOX
, or
ADVC
options
•
BACK
to choose another
commissioning function
•
EXIT
to return to the temperature
display.
2. Press the button to select the next
function.
Procedure to set the commissioning setpoints (Continued)
Procedure
Steps
STE display
Set
Point
O5
DIFF
Set
Point
OS
Set
Point
OO
DDOF
Set
Point
OO5
DDDP
Set
Point
1OOO
C2SP
Set
Point
STPT