Revision A

Commissioning functions
Balancing airflow

30

Measure and enter
the actual
minimum
secondary airflow

The display begins flashing SMIN
and also displays the actual airflow
at the bottom.

Note:

The airflow displayed by the

STE-8000 in this step is the actual,
uncorrected airflow.

1. Wait for the minimum airflow value

to stabilize.

2. With a flow hood, measure the actual

airflow.

3. Press the button to advance to the

entry display. SMIN stops flashing.

4. Press the or buttons to enter the

measured airflow.

5. Press the button to save the

measured airflow. The display
advances to SEC.

Advance or exit

1. Press the or buttons to select

one of the following

PRI

to balance the primary VAV

for dual duct systems

BACK

to choose another

commissioning function

EXIT

to return to the temperature

display.

2. Press the button to select the next

function.

The airflow balancing procedure (Continued)

Procedure

Steps

STE display

Set

Point

Set

Point

SMIN

OO

Set

Point

SEC