PNEU-DD-IOM-1.0 8-9-02

Dual Duct Models with TITUS II and IIA Pneumatic Controls

Installation, Operation, and Maintenance Manual

Adjusting Minimum and Maximum Air Flow for Units with Two Inlet Sensors

A. Maximum Flow Adjustment for

Direct Acting Thermostat

1. Be sure the minimum LO air flow

limit is zero on hot and cold deck

controller.

2. To adjust the cold deck maximum

CFM:

a. A p p l y 1 5 - 2 5 P S I t o t h e

thermostat connection on the

cold deck controller. Place a

m a n o m e t e r g a u g e a c r o s s

balancing tees at the cold deck

inlet.

b. I f t h e m a n o m e t e r g a u g e

reading matches the r equired

differential from the calibration

c u r v e ( P a g e 6 a n d 7 ) n o

adjustment is necessary.

c.

If adjustment is necessary, use

the adjusting tool stored in the

face of the controller (Titus II

only) or a standard flat blade

screwdriver.

d. Rotate the maximum HI knob

slowly. A delay in response

time has been deliberately built

i n t o t h e c o n t r o l s t o a v o i d

hunting. Allow several sec onds

for the controls to react and the

system to stabilize. Rotate the

knob until the gauge shows the

required differential pressure.

N O T E : I f t h e a c t u a t o r f a i l s t o

r e s p o n d , s e e G u i d e t o S e r v i c e

Procedures.

3. To adjust the hot deck maximum

CFM:

a. Apply 0 PSI to the thermostat

c o n n e c t i o n o n t h e c o l d d e c k

controller. That is, leave it open to

the atmosphere.Place a manometer

gauge across balancing tees at the

cold deck inlet.

b. Repeat Steps B, C and D above.

B. Maximum Flow Adjustment for

Reverse Acting Thermostat

1. To adjust the cold deck maximum

CFM:

a. Apply 0 PSI to the thermostat

connection on the cold deck

controller. That is, leave it open

to the atmosphere. Place a

m a n o m e t e r g a u g e a c r o s s

balancing tees at the cold deck

inlet.

b. Re p e a t s t e p s B , C a n d D

above.

2. To adjust the hot deck maximum

CFM:

a. A p p l y 1 5 - 2 5 P S I t o t h e

thermostat connection on the

hot deck. Place the manometer

gauge across balancing tees at

the hot deck inlet.

b. Re p e a t s t e p s B , C a n d D

above.

C. Minimum Flow Adjustment for

Either Thermostat

1. Place a 0-30 PSI pressure

gauge in

the line between the TITUS I I

Controller and the damper actuator

on the cold deck.

2. Place a manometer gauge across

the balancing tees on the hot deck

inlet.

3. Adjust the thermostat pressure

( P r e s s u r e r e d u c i n g v a l v e

recommended) until the cold deck

damper just closes:

a. If the damper in the cold deck

is normally open, the pressure

g a u g e s h o u l d r e a d

approximately 10 PSI with

standard 5-10 PSI actuator.

b. If the damper in the cold deck

i s n o r m a l l y c l o s e d , t h e

pressure gauge should read

a p p r o xi m a t e l y 5 P S I wi t h

standard 5-10 PSI actuator.

4. Refer to Page 6 an d 7 f o r t h e

differential pressure corresponding

to the desired minimum air flow

(CFM).

5. Adjust the reset start point dial on

the hot deck until the manometer

gauge across the balancing tees

on the hot deck reads the desired

differential pressure.

D. After Flow Rates are Adjusted

1. Replace the thermostat connection

at the controller, if it has been

removed during the adjustment

process.

2. Remove the m anometer gauge and

replace the caps on the tees in the

HI and LO tubes.

NOTE: The controller w

ill not operate

if these caps are left off.

3. Return the adjustment tool to its

socket in the face of the controller.

4. R e p l a c e t h e c o v e r s o v e r t h e

controllers.

B

Cold

TSTAT

MAIN

M

T

Hi

Lo

B

Hot

Hi

Lo

M

T

Figure 1. Piping Diagram

Figure 2. Control Box Label

MODEL NO.

PEDV

SIZE:

6

MAX CFM:

400

MIN CFM: 0

COLD INLET CFM:

400

VP:

0.63

HOT INLET CFM:

400

VP:

0.63

HAND (COLD INLET LOCATION):RH
LOCATION:

XXXX

FACTORY NO.

XXXX

ITEM:

XXXX

MOTOR:

XXXX

THST:

DIRECT ACTING

Inlet Size, Inches
Minimum CFM
Cold Deck Max Velocity Pressure, Inches WG
Hot Deck Max Velocity Pressure, Inches WG
Same as Number as on Packing List
Actuator Mfr.
Thermostat Action