Electrical specifications – SDC 1580 SERIES EMLOCK User Manual

Page 2

background image

N/C ORG COVER OFF

N/O YEL COVER ON

COM WHT

ATS

TD

TIME ADJ.

L-3

-

+
+

GRN

BRN

RED

BAS

AVAILABLE OPTIONS

ATS

BAS
DPS

LED

TD

Anti-Tamper Switch
Magnetic Bond Sensor
Door Position Switch
Tri-Color LED Red or Green
Both on = Yellow
TIME DELAY (1-30 sec)

SPDT, DRY,
SPDT, DRY,
SPDT, DRY,
20 mA
40 mA
20 mA

L-3

-

+
+

GRN

BRN

RED

BAS

BAS
DPS

LED

Magnetic Bond Sensor
Door Position Switch
Tri-Color LED Red or Green
Both on = Yellow

SPST, No, Dry
SPDT, Dry
20 mA
40 mA

All switches rated @ 250 mA @ 30 VDC

AVAILABLE OPTIONS

ELECTRICAL INSTALLATION

IMPORTANT NOTES

1. Use jacketed cable for all wire runs. Refer to the SDC wire
gauge chart for proper lock power wire size (18 AWG
gauge minimum).

2. Use only shielded cable for all signal wires. 22 AWG gauge
(minimum) may be used for signal wires up to 1,000 feet.

3. All wires must be colored coded.

4. Use properly fused power source only. See Electrical
Specifications.

5. Make all Emlock terminal connections according to
Figure 3A or 3B.

INDOOR USE ONLY
Do not run power wires and signal wires in the same cable or
conduit.

Do not install a diode in parallel with any magnetic lock. A diode
will cause a delay when releasing the door and residual
magnetism to occur.

Although SDC recommends the use of a DC power supply, a
transformer with an adjacent mounted full wave bridge rectifier
may be used. A significant voltage drop will occur when using a
full wave bridge rectifier.

Any low voltage condition will cause erratic operation of the
optional bond sensor.

When using a full wave bridge rectifier, all access controls and/or
release contacts must be located between the Emlock and rectifier
to ensure quick release.

P:\INSTALLATION INST\Electromagnetic Locks\INST-1500-10-70-80.vsd REV E 04-06 Page 2

COM GRN

N/O BLU

ELECTRICAL SPECIFICATIONS

Voltage kickback protection standard

SERIES

INPUT VOLTAGE (VDC)

POWER CONSUMPTION (mA)

COIL RESISTANCE (OHMS)

HOLDING FORCE (LBS)

1510

12/24

700/350

1650

35 (PER COIL)

*

1570

12/24

250/125

1200

100 (PER COIL)

*

1580

12/24

440/220

650

60 (PER COIL)

*

*NOTE: For a proper coil resistance reading, turn off the DC voltage. Use an ohmmeter and measure
the resistance between the pins of the plug connector positions E1-E2 and E3-E4

OPTIONAL: 1511-DF DRILL FIXTURE
Drill many doors and frames in a fraction of the time.

1511-DF

1510, 1570 SERIES CONNECTIONS

LOCK PWR

-

+

NC

OPEN

COM

NO

CLOSED

-
-

DPS

NC

UNLOCKED

COM

NO

LOCKED

-
-

BAS

ELECTROMAGNET

PLUG CONNECTION

FIG. 3A

BAS PLUG IN

EMLOCK

E4

E3

E2

E1

1580 SERIES CONNECTIONS

LOCK PWR

-

+

NC

OPEN

COM

NO

CLOSED

-
-

DPS

NOT USED

ELECTROMAGNET

PLUG CONNECTION

FIG. 3B

EMLOCK

E4

E3

E2

E1

J1