Oxygen Transmitter • 6

Pioneer Operator’s Manual (PRELIMINARY)

Wiring the Oxygen Transmitter to the Pioneer

WARNING: Always verify that the Pioneer’s power switch is in the OFF position

before you make wiring connections.

1.

Place the Pioneer’s power switch in the OFF position.

2.

Loosen the two securing screws from the

detector

junction box cover, then remove the

cover.

3.

Unscrew and remove the

amplifier

junction box cover.

4.

In the

detector

junction box, verify that the leads from the sensor connector are wired

to the (2-point) sensor terminal block.

5.

In the

amplifier

junction box, verify that the wiring from the opposite side of the

(2-point) sensor terminal block is wired to the amplifier’s detector terminal strip.

If necessary, connect the sensor terminal block and detector terminal strip as shown in
Figure 3.

6.

Verify that the jumper block is installed over the

OXY

selector of the amplifier type

selector as shown in Figure 3.

7.

Guide a two-conductor, shielded cable or two wires in conduit through the top
conduit hub of the junction box.

8.

Connect the two wires to the interconnect terminal strip as follows (see Figure 3.)

Connect the positive wire to the terminal labeled

24V +

.

Connect the feedback wire to the terminal labeled

4/20 FB

.

CAUTION:

Leave the ground wire insulated and disconnected at the transmitter. You will

connect the opposite end of the cable’s ground wire at the Pioneer.

9.

Secure the

detector

junction box cover to the junction box with the two screws you

removed in step 2.

10. Secure the

amplifier

junction box cover to the junction box.

11. Route the cable or wires leading from the oxygen transmitter through one of the

conduit hubs on the bottom of the Pioneer housing.

CAUTION:

Do not route power and transmitter wiring through the same conduit hub. The

power cable may disrupt the transmission of the transmitter signal to the Pioneer.