Pioneer Operator’s Manual (PRELIMINARY)
Combustible Gas Transmitter • 21
Slow or No Response/Difficult or Unable to Calibrate
Symptoms
•
The transmitter responds slowly or does not respond during the monthly response
test.
•
Unable to accurately set the zero or response reading during the calibration
procedure.
•
The transmitter requires frequent calibration.
NOTE:
Under “normal” circumstances, the transmitter requires calibration once every
three months. Some applications may require a more frequent calibration
schedule.
Probable causes
•
The calibration cylinder is low, out-dated, or defective.
•
The transmitter is malfunctioning.
Recommended action
1.
Verify that the calibration cylinder contains an adequate supply of a fresh test sample.
2.
If the calibration/response difficulties continue, replace the detector as described later
in this section.
3.
If the calibration/response difficulties continue, contact RKI Instruments, Inc., for
further instruction.
No Display Reading
Symptoms
•
The transmitter is installed, but the display screen is blank for that channel.
NOTE:
If the display screen is blank for all channels, see the troubleshooting guide in
Chapter 5, Maintenance.
Probable causes
•
The channel status setting is set at NO SENSOR/AMP.
Recommended action
1.
Enter the Channel Setup program, and change the channel status setting to ACTIVE/
ONLINE
or SILENCED/OFFLINE.
2.
If the display reading difficulties continue, contact RKI Instruments, Inc., for further
instruction.