Lenze SCD Series User Manual
Page 91

88
NOTE 2: Preset speeds are accepted only when DeviceNet control is set but NOT network reference.
If network reference is set, preset speed control is ignored. To simplify setup, refer to the following
parameters in the EDS file: Parameter 24 - DeviceNet Preset Command, and Parameter 38 - Keypad
Command Frequency.
NOTE 1: Refer to the following table for Frequency Source Bits representation.
BIT 2
BIT 1
BIT 0
SPEED SOURCE
0
0
0
LOCAL (keypad, analog)
0
0
1
PRESET SPEED #1
0
1
0
PRESET SPEED #2
0
1
1
PRESET SPEED #3
1
0
0
PRESET SPEED #4
1
0
1
PRESET SPEED #5
1
1
0
PRESET SPEED #6
1
1
1
PRESET SPEED #7
PRESET SPEED BITS REPRESENTATION
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
0
NET.
NET.
FAULT
RUN
RUN
REF.
CONTROL
RESET
REV
FWD
1
2
3
21 EXTENDED SPEED CONTROL OUTPUT ASSEMBLY
SPEED REFERENCE RPM (LOW BYTE)
SPEED REFERENCE RPM (HIGH BYTE)
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
0
NET.
NET.
FAULT
RUN
RUN
REF.
CONTROL
RESET
REV
FWD
1
2
3
100 AC TECH EXTENDED SPEED CONTROL OUTPUT ASSEMBLY
SPEED REFERENCE Hz (LOW BYTE)
SPEED REFERENCE Hz (HIGH BYTE)
BYTE
BIT 7
BIT 6
BIT 5
BIT 4
BIT 3
BIT 2
BIT 1
BIT 0
0
FAULT
RUN
RUN
RESET
REV
FWD
1
PRESET
PRESET
PRESET
BIT 2
BIT 1
BIT 0
103 AC TECH PRESET SPEED CONTROL OUTPUT ASSEMBLY