Lenze SCD Series User Manual
Page 17

14
THREE PHASE INPUT
(SD200, SD200Y, SD400,
AND SD500 SERIES)
3 PHASE
AC MOTOR
208/240 Vac SINGLE PHASE INPUT
(SD200Y SERIES)
DC BUS
VOLTAGE
OUTPUT (ALL SERIES)
L1
L2
L3
T1 T2 T3 B- B+
+
NOTES:
1.
WIRE AND GROUND IN ACCORDANCE WITH NEC OR CEC, AND ALL APPLICABLE
LOCAL CODES.
2.
Motor wires MUST be run in a separate steel conduit away from control wiring and incoming AC
power wiring.
3.
Do not install contactors between the drive and the motor without consulting AC Technology for
more information. Failure to do so may result in drive damage.
4.
Use only UL and CSA listed and approved wire.
5.
Minimum wire voltage ratings: 300 V for 208 and 240 Vac systems, and 600 V for 400, 480, and
590 Vac systems.
6.
Wire gauge must be based on a minimum of 125% of the rated input/output current of the drive,
and a minimum 75°C insulation rating. Use copper wire only.
7.
Strip off 0.20 to 0.25 inches (5 to 6 mm) of insulation for input power, output power, and DC Bus
wiring.
9.0
SCD POWER WIRING DIAGRAM
WARNING!
Do not connect incoming AC power to output terminals T1, T2, or T3. Severe damage to the drive
will result.
L1
L2
L3