31
FACTORY
NO.
PARAMETER NAME
RANGE OF ADJUSTMENT
DEFAULT
(NOTE 1)
40
FREQUENCY SCALING
3.0 - 2000.0 Hz
60.0 Hz
41
LOAD SCALING
10 - 200 %
200 %
42
ACCEL / DECEL #2
0.1 - 3600.0 SEC
20.0 SEC
44
PASSWORD
000 - 999
225
47
CLEAR HISTORY
MAINTAIN (01), CLEAR (02)
MAINTAIN (01)
48
PROGRAM
USER SETTINGS (01), OEM SETTINGS (02),
USER
SELECTION
RESET OEM (03), RESET 60 (04),
SETTINGS (01)
RESET 50 (05), TRANSLATE (06)
50
FAULT HISTORY
(VIEW-ONLY)
(N/A)
51
SOFTWARE CODE
(VIEW-ONLY)
(N/A)
52
DC BUS VOLTAGE
(VIEW-ONLY)
(N/A)
53
MOTOR VOLTAGE
(VIEW-ONLY)
(N/A)
54
LOAD
(VIEW-ONLY)
(N/A)
55
0-10 VDC INPUT
(VIEW-ONLY)
(N/A)
56
4-20 mA INPUT
(VIEW-ONLY)
(N/A)
57
TB STRIP STATUS
(VIEW-ONLY)
(N/A)
58
KEYPAD STATUS
(VIEW-ONLY)
(N/A)
59
TB-30 OUTPUT
(VIEW-ONLY)
(N/A)
60
TB-31 OUTPUT
(VIEW-ONLY)
(N/A)
85
MOTOR RATED RPM
1 - 65000 RPM
1800 RPM
86
MOTOR RATED AMPS
0.0 - 999.9 AMPS
100.0 AMPS
87
MOTOR RATED VOLTS
0 - 1000 VOLTS
100 VOLTS
88
MOTOR RATED FREQ
0 - 1000 Hz
60 Hz
89
DRIVE RATED AMPS
0.0 - 999.9 AMPS
100.0 AMPS
90
DRIVE RATED VOLTS
0 - 1000 VOLTS
100 VOLTS
PARAMETER MENU (CONT’D)
NOTE 1:
Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.