Lenze SCD Series User Manual
Page 76

73
The SCD parameters that are accessible through the network are separated into 4 groups: Monitor and
Control, Program, DNET Config, and Motor Data. The same groups are implemented in the EDS file.
IMPLEMENTED PARAMETER GROUPS:
B.5.7
PARAMETER GROUP OBJECT - CLASS 0x10
ATTRIBUTE ID ACCESS RULE
NAME
DATA TYPE
VALUE
1
GET
REVISION
UINT
1
2
GET
NUMBER OF
UINT
4
INSTANCES
8
GET
NATIVE LANGUAGE
UINT
0 = English
1
GET
GROUP NAME
SHORT
STRING
2
GET
NUMBER OF MEMBERS
UINT
IN THE GROUP
3
GET
1st PARAMETER
UINT
IN THE GROUP
4
GET
2nd PARAMETER
UINT
IN THE GROUP
n
GET
(n-2) th PARAMETER
UINT
IN THE GROUP
PARAMETER GROUP CLASS ATTRIBUTES
INSTANCE 0
INSTANCE 1 - 3
ID
ID
1
OUTPUT FREQUENCY (0.1 Hz)
30
RUN STATE
2
OUTPUT VOLTAGE (V)
31
SPEED SOURCE
3
OUTPUT CURRENT (100mA)
33
AT REFERENCE STATUS
4
OUTPUT POWER (W)
20
CONTROL SOURCE
5
INPUT VOLTAGE (V)
21
RUN FORWARD
6
COMMANDED FREQUENCY (0.1 Hz)
22
RUN REVERSE
7
PRESENT FAULT DNET CODE
23
FAULT RESET
8
PRESENT FAULT NAME
24
DEVICENET PRESET COMMAND
27
STATUS OF RUN/STOP CONTROL SRC
25
SPEED REFERENCE
28
STATUS OF SPEED REFERENCE
26
NETWORK REFERENCE FREQUENCY
29
ACTUAL DIRECTION
38
KEYPAD COMMAND FREQUENCY
GROUP 1 - INSTANCE 1
NAME: "MONITOR AND CONTROL"
PARAMETER
PARAMETER