Lenze SCD Series User Manual
Page 33

30
FACTORY
NO.
PARAMETER NAME
RANGE OF ADUSTMENT
DEFAULT
(NOTE 1)
12
TB-13C FUNCTION
NONE (01), 0-10 VDC (02), 4-20 mA (03),
NONE (01)
SELECT
PRESET SPEED #3 (04), INCREASE FREQ (05),
EXTERNAL FAULT (06), Factory Reserved (07),
DB FAULT (08), ACCEL/DECEL #2 (09)
13
TB-15 OUTPUT
(SEE PARAMETER 6 - TB-14 OUTPUT)
NONE (01)
14
CONTROL
TERMINAL STRIP & DEVICENET (01),
TERMINAL STRIP &
DEVICENET ONLY (02),
DEVICENET (01)
16
UNITS EDITING
TENTHS OF UNITS (01),
WHOLE
WHOLE UNITS (02)
UNITS (02)
17
ROTATION
FORWARD ONLY (01),
FORWARD
FORWARD AND REVERSE (02)
ONLY (01)
19
ACCELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
20
DECELERATION TIME
0.1 - 3600.0 SEC
20.0 SEC
21
DC BRAKE TIME
0.0 - 3600.0 SEC
0.0 SEC
22
DC BRAKE VOLTAGE
0.0 - 30.0 %
0.0 %
23
MINIMUM FREQUENCY
0.0 - MAXIMUM FREQUENCY
0.0 Hz
24
MAXIMUM FREQUENCY
MINIMUM FREQ - 240.0 Hz (NOTE 2)
60.0 Hz
25
CURRENT LIMIT
30 - 180 % (NOTE 3)
180%
26
MOTOR OVERLOAD
30 - 100 %
100%
27
BASE FREQUENCY
25.0 - 500.0 Hz (NOTE 4)
60.0 Hz
28
FIXED BOOST
0.0 - 30.0 %
1.00%
29
ACCEL BOOST
0.0 - 20.0 %
0.00%
30
SLIP COMPENSATION
0.0 - 5.0 %
0.00%
31-37
PRESET SPEEDS
0.0 - MAXIMUM FREQUENCY
0.0 Hz
38
SKIP BANDWIDTH
0.0 - 10.0 Hz
0.0 Hz
39
SPEED SCALING
0.0 - 6500.0
0
PARAMETER MENU (CONT’D)
NOTE 1:
Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base frequency.
NOTE 2:
Maximum setting is 999.9 Hz on drives with High Output Frequency option. Consult the factory.
NOTE 3:
If LINE VOLTAGE is set to LOW, maximum setting is 150%.
NOTE 4:
Maximum setting is 1300.0 Hz (factory default is 999.9) on drives with High Output Frequency option.
Consult the factory.