Lenze SCD Series User Manual
Page 87

84
DNET Par. ID 25 - SPEED REFERENCE:
0 - Local speed reference (SCD drive speed selection: keypad, presets, analog)
1 - Network speed reference
Object Map - AC Drive Object 0x2A-1-4
NOTE: Parameter IDs 20-25 will reset to 0 when power is cycled or the drive is reset.
DNET Par. ID 26 - NETWORK COMMAND FREQUENCY: Sets the drive command frequency
if parameter ID #25 is set to NETWORK REFERENCE (0.1 Hz resolution).
DNET Par. ID 27 - CONTROL SOURCE (READ ONLY)
0 - Local control
1 - Control from the Network
Object Map - Control Supervisor Object 0x29-1-15
DNET Par. ID 28 - SPEED REFERENCE SOURCE (READ ONLY)
0 - Local speed reference
1 - Network speed reference
Object Map - AC Drive Object 0x2A-1-29
DNET Par. ID 29 - DRIVE ACTUAL DIRECTION (READ ONLY)
0 - Forward
1 - Reverse
DNET Par. ID 30 - RUN STATUS (READ ONLY): See table below:
DNET Par. ID 31 - SPEED SOURCE (READ ONLY): See table below:
NO.
NO.
NO.
STATUS
0
FAULT LOCKOUT
4
DC BRAKE
8
DECELERATION
1
FAULT
5
RUN AT 0 Hz
9
CURRENT LIMIT
2
START PENDING
6
RUN
10
DECEL OVERRIDE
3
STOP
7
ACCELERATION
11
LOWER ON SEQUENCE
STATUS
STATUS
RUN STATUS
NO.
NO.
NO.
0
KEYPAD
5
PRESET SPEED #3
10
JOG SPEED
1
0 - 10 VDC
6
PRESET SPEED #4
11
MOP SPEED
2
4 - 20 mA
7
PRESET SPEED #5
12
DEVICENET
3
PRESET SPEED #1
8
PRESET SPEED #6
4
PRESET SPEED #2
9
PRESET SPEED #7
SOURCE
STATUS
SPEED SOURCE
STATUS