20
11.3
ALTERNATE TWO-WIRE START/STOP CONTROL
Shown below is the wiring diagram for an alternate two-wire start/stop control scheme, using one
maintained contact for RUN FORWARD and another maintained contact for RUN REVERSE.
NOTES:
1.
For this control scheme, TB-13A MUST be set to RUN REVERSE (05), even if REVERSE
direction is not required. Refer to Parameter 10 - TB13A FUNCTION.
2.
Close TB-12 to TB-4 to RUN in forward direction, and open TB-12 to TB-4 to STOP.
3.
If reverse direction is also required, ROTATION DIRECTION (Parameter 17) must be set to
FORWARD AND REVERSE (02). Close TB-13A to TB-4 to RUN in REVERSE, and open TB-
13A to TB-4 to STOP. If TB-12 and TB-13A are both closed to TB-4, the drive will STOP.
4.
For 0-10 VDC or 4-20 mA speed control, use one of the following methods:
1.
Program one of the TB-13 terminals (13A, 13B, or 13C) for 0-10 VDC (02) or 4-20 mA (03).
When that TB-13 terminal is closed to TB-4, the drive will respond to the selected speed
reference signal. If that TB-13 terminal is not closed to TB-4, the drive will respond to the
speed control source selected in Parameter 05 - STANDARD SPEED SOURCE. This method
must be used if it is necessary to toggle between two speed reference sources.
2.
Program Parameter 05 - STANDARD SPEED SOURCE for 0-10 VDC (03) or 4-20 mA (04).
This method is preferable if only one speed reference source is required, as this method
leaves the TB-13 terminals free to be used for other functions.
STOP
DIGITAL INPUT REF.
0-10 VDC or 4-20 mA INPUT
RUN FWD
COMMON
RUN REV
0-10 VDC or 4-20 mA SELECT
1
4 5/25 11
2
CAN+ V+
14
13B 13C 15
13A
30
V-
12
31
SHLD
CAN-
FWD
REV
DEVICENET
TM
INTERFACE
Removable Connector
(Refer to Appendix B)