Lenze SCD Series User Manual
Page 51

48
P87
MOTOR RATED VOLTAGE
When using the DeviceNet interface, this must be set to match the nameplate voltage rating of the
motor.
P88
MOTOR RATED FREQUENCY
When using the DeviceNet interface, this must be set to match the nameplate frequency rating of the
motor.
P89
DRIVE RATED CURRENT
When using the DeviceNet interface, this must be set to match the nameplate output current rating of
the drive.
P90
DRIVE RATED VOLTAGE
When using the DeviceNet interface, this must be set to match the nameplate maximum output voltage
rating of the drive.
Example: A 5 Hp, 400/480 Vac SCD drive (SD450) is being used with a 5 Hp, 230/460 Vac, 60 Hz,
1800 RPM motor that is rated 7.1 amps. Parameters 85-90 would be set as follows:
P85
MOTOR RATED RPM
1800 RPM
P86
MOTOR RATED CURRENT
7.1 AMPS
P87
MOTOR RATED VOLTAGE
460 VOLTS
P88
MOTOR RATED FREQUENCY
60 Hz
P89
DRIVE RATED CURRENT
7.6 AMPS
P90
DRIVE RATED VOLTAGE
480 VOLTS
C00
DEVICENET NODE ADDRESS
C01
DEVICENET BAUD RATE
C02
DEVICENET LOSS ACTION
C03
DEVICENET OUTPUT ASSEMBLY SELECTION
C04
DEVICENET INPUT ASSEMBLY SELECTION
C05
DEVICENET CUSTOM INPUT ASSEMBLY WORD 0
C06
DEVICENET CUSTOM INPUT ASSEMBLY WORD 1
C07
DEVICENET CUSTOM INPUT ASSEMBLY WORD 2
C08
DEVICENET CUSTOM INPUT ASSEMBLY WORD 3
C09
DEVICENET MOTOR TYPE
C10
DEVICENET DIAGNOSTICS
NOTE: Refer to Appendix B - DeviceNet Control for more information on Parameters 85-90 and
C00 - C10.