Lenze SCD Series User Manual
Page 81

78
If Attribute #5 NET CONTROL is set to 1, the RUN and STOP events are triggered according to the
following event table:
NOTE: If ACT PARAMETER #17 DIRECTION is set to FORWARD ONLY, the drive will not be
able to run in the reverse direction.
ATTRIBUTE ID ACCESS RULE
NAME
DATA TYPE
VALUE
1
GET
NO. OF SUPPORTED
USINT
16
ATTRIBUTES
2
GET
ATTRIBUTE LIST
ARRAY
3
GET / SET
RUNFWD
BOOL
0 to 1
4
GET / SET
RUNREV
BOOL
0 to 1
5
GET / SET
NETCTRL
BOOL
0 to 1
6
GET
STATE
UINT
3 = Ready
4 = Enabled
7 = Faulted
7
GET
RUNNINGFWD
BOOL
0 to 1
8
GET
RUNNINGREV
BOOL
0 to 1
9
GET
READY
BOOL
0 to 1
10
GET
FAULTED
BOOL
0 to 1
11
GET
WARNING
UINT
0 (Not Supported)
12
GET / SET
FAULTRST
BOOL
0 to 1
13
GET
FAULT CODE
UINT
0 to 65535
15
GET
CTRLFROMNET
USINT
0 to 1
16
GET / SET
ACTION ON LOSS
USINT
0 = Fault
OF DEVICENET
1 = Ignore Comm. Fault
2 = AC Tech Specific
17
GET / SET
FORCE TRIP
BOOL
0 to 1
INSTANCE 1
CONTROL SUPERVISOR CLASS ATTRIBUTES
The drive shows the "nF" fault on the LED display
ATTRIBUTE RUN FWD
ATTRIBUTE RUN REV
TRIGGER EVENT
RUN TYPE
0
0
STOP
N/A
0 --> 1
0
RUN
RUN FORWARD
0
0 --> 1
RUN
RUN REVERSE
0 --> 1
0 --> 1
NO ACTION
N/A
1
1
NO ACTION
N/A
1 --> 0
1
RUN
RUN REVERSE
1
1 --> 0
RUN
RUN FORWARD