Parameterisation 8200 vector/8200 motec
Transmit parameter sets
EDK9371BC DE/EN/FR 3.1
81
l
H1 Parametrierung 8200−9371BC_6L
Copy parameter sets from the keypad to the standard device
Step
Key sequence
Action
1.
Connect the keypad to
standard device 2
2.
Inhibit the controller
S
The drive coasts
3.
Select the "Load/Store"
submenu 7.1 in the "Param
managm" menu 7
z y Z Y
Change to the "Load/Store" submenu
using the arrow keys
4.
Change to the code level
Z
"Param managm" is displayed in C0002
5.
Change to the parameter level
V
"0" and "READY"are displayed
6.
Select the correct copy function
The settings stored in the standard
device or in the function module are
overwritten.
l
Copy all available parameter sets (PAR1 ... PAR4, FPAR1 if applicable) into the standard
device:
– Standard device with
function module
Application I/O,
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen
z
Copy PAR1 ... PAR4 and FPAR1:
ð
Set "70" "Key−>F1&PAR1−4"
– Standard device with all
other function modules
Copy PAR1 ... PAR4:
ð
Set "10" "Keypad−>PAR1−4"
l
Only copy the module−specific parameter set FPAR1 to the function module:
– Only possible for
standard devices with
function module
INTERBUS,
PROFIBUS−DP, LECOM−B,
DeviceNet, CANopen:
z
Copy FPAR1:
ð
Set "40" "Keypad−>FPAR1"