8 Configuration level

93

2013-04-01

8.3.2 Switching behavior

Min. alarm:
If the value falls below the limit value, the alarm relay
output switches OFF. LEDs K1 and K2 light up red and
the measured values flash on the display.

Max. alarm, min. alarm

In the

safety temperature limiter (STB) setting, this condition remains even when the main mea-

sured value is back in the valid range. Only when the "Reset" key is pressed or a switch is acti-
vated when the binary input is respectively configured will the alarm relay output switch ON
again and the OK LED light up green.
In the

safety temperature monitor (STW) setting, the alarm relay output automatically switches

back to ON as soon as the main measured value is back within the valid range.

Parameter

Comment

Value range
(factory setting in

bold)

S

P

14

16

15

Ö

3,15A

S

P

14

16

15

Ö

3,15A

Hyster

esis

Hyster

esis

S

P

11

12

13

Ö

Min. alarm

(

direct or S-Function)

older devices:

Relay output pre-alarm

active

(KV)

Relay output pre-alarm
(KV) inaktive

Relay output alarm active

Relay output alarm inactive

Pre-alarm range

Alarm range

Valid range

Limit Value

Min. set.range

Max. set.range

Measured value

Measured value

Distance from limit value Pre-alarm (absolute value)

LED KV lights up yellow

LED K1, K2 light up red

LED OK lights up green