2 switching behavior, Switching behavior, 8 configuration level – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 99: Min. alarm

8 Configuration level
93
8.3.2 Switching behavior
Min. alarm:
If the value falls below the limit value, the alarm relay
output switches OFF. LEDs K1 and K2 light up red and
the measured values flash on the display.
Max. alarm, min. alarm
In the
safety temperature limiter (STB) setting, this condition remains even when the main mea-
sured value is back in the valid range. Only when the "Reset" key is pressed or a switch is acti-
vated when the binary input is respectively configured will the alarm relay output switch ON
again and the OK LED light up green.
In the
safety temperature monitor (STW) setting, the alarm relay output automatically switches
back to ON as soon as the main measured value is back within the valid range.
Parameter
Comment
Value range
(factory setting in
bold)
S
P
14
16
15
Ö
3,15A
S
P
14
16
15
Ö
3,15A
Hyster
esis
Hyster
esis
S
P
11
12
13
Ö
Min. alarm
(
direct or S-Function)
older devices:
Relay output pre-alarm
active
(KV)
Relay output pre-alarm
(KV) inaktive
Relay output alarm active
Relay output alarm inactive
Pre-alarm range
Alarm range
Valid range
Limit Value
Min. set.range
Max. set.range
Measured value
Measured value
Distance from limit value Pre-alarm (absolute value)
LED KV lights up yellow
LED K1, K2 light up red
LED OK lights up green