10 determining the achieved performance level (pl), Determining the achieved performance level (pl), 6 safety manual – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual
Page 53

6 Safety Manual
47
6.10 Determining the achieved Performance Level (PL)
The following safety-related parameters are required to determine the Performance Level of components/devices:
As further parameters to be observed, operational aspects such as the demand rate and/or the test rate of the safety function
can also influence the resulting PL.
Excerpt from DIN EN ISO 13849-1:2008-12
Average failure probability of a safety
function on demand (overall system)
SIL2:
Low demand: PFD
avg
< 10
-2
High demand: PFH < 10
-6
SIL3:
Low demand: PFD
avg
< 10
-3
High demand: PFH < 10
-7
Interval for repeat test
No repeat test
Planned operating duration
10 years
Architecture according to DIN EN ISO
13849-1
Sensor system, one-channel: Cat. 2
Sensor system, two-channel: Cat. 3
MTTF
d
-DC
avg
according to DIN EN
ISO 13849-1 Table K.1
PL d:
≥
62 years DC
avg
≥
60 %
PL e:
≥
62 years DC
avg
≥
90 %
Mode of operation and software
class according to DIN EN 14597
The JUMO safetyM STB/STW Ex possesses the following modes of operation:
2B, 2D, 2F, 2K, 2J, 2V, 2N, 2P software class C
H
This excerpt contains references to the complete standard DIN EN ISO 13849-1:2008-12, which are therefore not
reproduced in this chapter.
Table 9:
Safety feature
Requirement / comment