6 Safety Manual

47

2013-04-01

6.10 Determining the achieved Performance Level (PL)

The following safety-related parameters are required to determine the Performance Level of components/devices:

As further parameters to be observed, operational aspects such as the demand rate and/or the test rate of the safety function
can also influence the resulting PL.

Excerpt from DIN EN ISO 13849-1:2008-12

Average failure probability of a safety
function on demand (overall system)

SIL2:
Low demand: PFD

avg

< 10

-2

High demand: PFH < 10

-6

SIL3:
Low demand: PFD

avg

< 10

-3

High demand: PFH < 10

-7

Interval for repeat test

No repeat test

Planned operating duration

10 years

Architecture according to DIN EN ISO
13849-1

Sensor system, one-channel: Cat. 2

Sensor system, two-channel: Cat. 3

MTTF

d

-DC

avg

according to DIN EN

ISO 13849-1 Table K.1

PL d:

62 years DC

avg

60 %

PL e:

62 years DC

avg

90 %

Mode of operation and software
class according to DIN EN 14597

The JUMO safetyM STB/STW Ex possesses the following modes of operation:
2B, 2D, 2F, 2K, 2J, 2V, 2N, 2P software class C

H

This excerpt contains references to the complete standard DIN EN ISO 13849-1:2008-12, which are therefore not
reproduced in this chapter.

Table 9:

Safety feature

Requirement / comment