9 Technical data

2013-04-01

106

9.2

Analog output

9.3

Binary input

9.4

Relay outputs

Signal type

Accuracy

Residual ripple

Load influence

Temperature

influ-

ence

Load

resis-

tance

Current

4 to 20 mA

0.5 %

±0.5 % at 300

Ω

±0.05 mA / 100

Ω

150 ppm/K

500

Ω

0 to 20 mA

Voltage

2 to 10 V

0.5 %

±0.5 %

±15 mV

150 ppm/K

÷

500

Ω

0 to 10 V

Connection

Function

1 potential-free contact

Unlocking, key lock, level inhibit can be configured

Relay output KV

Relay (changeover contact) without contact protection
30000 switching operations at a switching capacity of AC 250 V/3 A, 50 Hz (resistive load)
or up to DC 30 V/3 A. Minimum current: DC 12 V/100 mA.

Relay output alarm

Relay (changeover contact)

Contact protection circuit: fuse cut-out 3.15 AT, installed in the N/O contact arm
30000 switching operations at a switching capacity of AC 230 V/3 A, 50 Hz (resistive load)
or up to DC 30 V/3 A. Minimum current DC 12 V/100 mA.