8 Configuration level

103

2013-04-01

8.7

Service

Parameter

Comment

Value range
(factory setting in

bold)

8.7.1 Limit switching cycle

Limit value for relay switching cycles

Here, the limit value for the admissible relay switching
cycles is set.
If the counter value for

Current switching cycles is

greater than this value, the display values flash and the
alarm relay output drops out.

If "0" is set the function is inactive.

0 to 99999

8.7.2 Current switching cycles

Relay switching cycle counter

Here, the switching cycles for the relay are only count-
ed if the top

limit value for relay switching cycles is

not set to "0" and is thus inactive.

The value can then be adjusted as required and there-
fore adapted accordingly to the plant.
The switching cycle counter remains at 99999.

0 to 99999

8.7.3 Operating hours

Operating hours counter

The counter adds up the operating hours during which
the device was connected to the voltage supply.

The value cannot be changed and can be used as a
measure of how long the device was actually in opera-
tion after leaving the factory.

0 to 99999