beautypg.com

9 technical data, 1 analog inputs, Technical data – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 110: Analog inputs, 9technical data

background image

9 Technical data

2013-04-01

104

9

Technical data

9.1

Analog inputs

RTD temperature probes

Thermocouples

Description

Measuring range

Accuracy

2/3-wire circuit

1

Ambient temperature

influence

Pt100 DIN EN 60751

-200 to +850 °C

0.5 % / 0.1 %

50 ppm/K

Pt1000 DIN EN 60751

-200 to +850 °C

0.5 % / 0.1 %

50 ppm/K

Connection type

2-wire, 3-wire circuit

Maximum lead wire resistance 30

Ω

Sampling rate

210 ms

Fault tolerance time

5 s time taken into account for all diagnostic tests

Input filter

Digital filter, 2nd order; filter constant can be set from 0 to 100 s

Special features

Individual probe Pt100 2-wire,
display can also be programmed in °F

Description

Measuring range

Accuracy

1

Ambient temperature influ-

ence

Fe-CuNi "L" DIN 43710

-200 to +900 °C

0.4 %

100 ppm/K

Fe-CuNi "J" DIN EN 60584

-200 to +1200 °C

0.4 %

100 ppm/K

Cu-CuNi "U" DIN 43710

-200 to +600 °C

0.4 %

100 ppm/K

Cu-CuNi "T" DIN EN 60584

-200 to +400 °C

0.4 %

100 ppm/K