6 Safety Manual

2013-04-01

32

6.3

Safety temperature limiter (STB)

The safety temperature limiter is a device that is permanently locked after responding.
Manual reset using the

key is possible once the probe temperature has fallen below / has exceeded the limit value by the

amount of the switching differential. Possible settings: monitoring for overrange or underrange.

Modes of operation:

-

Minimum requirements: 2B, 2J, 2V, 2K, 2P, and adjustable with special tools

-

Additional requirements met: 2N, 2F, 2D

6.3.1

Safe operating status STB

The safe status is when the alarm relay output between terminals 14 and 16 is switched off (closed-circuit principle).

This status is maintained until manual unlocking in the valid range of the JUMO safety

M STB/STW Ex.

The transparent, sealable protective cover prevents unauthorized operation.

The

key for manual unlocking can be accessed with the aid of a tool.

6.4

Relevant standards

Failure of the devices could affect the safety of persons and/or the safety of the environment.

Certification according to IEC 61508 is provided due to the worldwide use of these systems.

The JUMO safety

M STB/STW Ex temperature monitoring unit with extra code "058" meets the requirements:

-

For safety function to SIL3 according to DIN EN 61508 Parts 1 to 7:
Functional safety of electrical/electronic/programmable electronic safety-related systems

-

DIN EN 61511 Parts 1 to 3:
Functional safety – safety instrumented systems for the process industry sector

-

DIN EN 14597:2005-12:
Temperature control devices and temperature limiters for heat generating systems

-

DIN EN 60730-2-9: