12 Error messages

2013-04-01

124

12 Error messages

These error messages are displayed one below the other.

Error display (Err)

Origin

Cause/remedy

Internal

The set limit value for relay switching cycles has been reached

h

Increase the limit value for the relay switching cycles

v

Chapter 8.7.1 "Limit switching cycle"

Instead of the bell, a cross appears and the error message can be acknowl-
edged.

Terminal temp.

Internal

The internal Pt100 is defective

1

, or the terminal temperature is outside the ad-

missible range (-10 to 80 °C).
This error cannot be acknowledged until it is within the admissible range
again.

Reference volt.

1

Internal

The reference voltage is outside the valid range.

Acknowledgement is not possible until it is within the valid range again.

Calibration const.

1

Internal

A calibration constant is outside the valid range.

Acknowledgement is not possible until it is within the valid range again.

Configuration

Internal

Configuration data outside the value range.

Acknowledgement is not possible until it is within the valid range again.

Measured value

Internal

The measured value 1 or 2 is outside the valid range.

Acknowledgement is not possible until it is within the valid range again.