beautypg.com

11 alarm messages, Alarm messages – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 129

background image

11 Alarm messages

123

2013-04-01

11 Alarm messages

These can appear as follows:

Alarm display

Cause

Remedy

5 flashing horizontal lines:

Measured value error
No valid value can be displayed

h

Check error messages on the device

h

Contact the JUMO Service department

v

Chapter 2.4 "Service addresses"

Measured value overrange
The measured value is too high, is out-
side the measuring range, or the probe
is broken.

h

Change the display to 2 measured values.
This makes it possible to detect which channel is de-
fective.

h

Check the probe and connecting cable for damage
or short circuit.

v

Chapter 4.3 "Connection diagram"

h

Check that the correct probe is set and/or connect-
ed.

v

Chapter 8.2 "Analog inputs"

Measured value underrange
The measured value is too low, is out-
side the measuring range, or a short cir-
cuit occurred at the probe.

5 flashing asterisks:

Display overflow
Value cannot be displayed

h

Check error messages on the device

h

Contact the JUMO Service department

v

Chapter 2.4 "Service addresses"