6 Safety Manual

45

2013-04-01

6.9.2

Safety-relevant system features

Device versions differ in the following architectures:

The evaluation unit of the JUMO safetyM STB/STW Ex in the STW and STB versions is implemented as 1oo2D architecture.

Figure 2: The types with a single sensor are executed in one-channel sensor systems (1oo1)

Figure 3: The variants with two sensors are consistently structured with two channels.

Systems have a lifetime of ten years.

The proof check for SIL2 and SIL3 certified systems is also ten years.

If the temperature is above/below the admissible limits, the system switches to the safe state without delay. Premature switch-
ing is admissible if a malfunction is detected.

The following are monitored:

-

Probe break

-

Probe short circuit

-

Random hardware failure in one channel

The following are monitored:

-

Probe break in sensor system subsystem

-

Probe short-circuit in sensor system subsystem

-

Reverse voltage polarity of the probes

-

Random hardware failure in one channel