beautypg.com

5 measuring circuit monitoring, 6 voltage supply, Measuring circuit monitoring – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 113: Voltage supply, 9 technical data, 5 measuring circuit monitoring 9.6 voltage supply

background image

9 Technical data

107

2013-04-01

9.5

Measuring circuit monitoring

9.6

Voltage supply

RTD temperature probe in 3-

wire circuit and

dual thermocouples

Thermocouples

Current 4 to 20 mA

Overrange
and underrange

Is detected
LEDs K1, K2, KD, and KV are lit;
">>>>" flashes in the display for overrange, "<<<<" for underrange

Probe and cable break

Is detected
LEDs K1, K2, KD, and KV are lit;
">>>>" flashes in the display; alarm relay output is inactive

LEDs K1, K2, KD, and KV are lit;
">>>>" flashes in the display;
alarm relay output is inactive

Probe short circuit

Is detected
LEDs K1, K2, KD, and KV are lit;
"<<<<" flashes in the display;
alarm relay output is inactive

Is detected

by difference

monitoring
of the analog inputs

v

Chapter 8.3.6 "Limit

value difference, hysteresis"

LEDs K1, K2, KD, and KV are lit;
"<<<<" flashes in the display;
alarm relay output is inactive

Voltage supply

AC/DC 20 to 30 V, 48 to 63 Hz

AC 110 to 240 V, +10/-15 %, 48 to 63 Hz

Power consumption

12 VA

Power loss

< 12 W