4 Electrical connection

17

2013-04-01

4.2

Removing the cover cap

V

The electrical connection and the configuration settings up to the startup must only be carried out by qualified per-
sonnel.

A

The approval according to DIN EN 14597 is only valid when the correct probe with DIN approval is set in the config-
uration level and if the probe is connected.

The limit value to be monitored must lie in the accepted temperature range of the DIN probe!

v

Chapter 9.13 "Probes for the operating medium air"

v

Chapter 9.15 "Probes for air, water, and oil"

The monitoring function is deactivated while data is transmitted over the setup program.

v

Chapter 13 "What to do, if ..."

1

h

Stick the screwdriver in the right open-
ing of the cover cap and pry up to the
left.

2

h

Hold the cover cap and pry up the sec-
ond catch in the left opening to the right.