Damage and corrosion of temperature probes – protection tubes

-

Corrosion and correct positioning of the contacts and terminals of cable connections

-

Seals of terminal heads and cable ducts

-

Interruptions due to "knocking" on the temperature probe/measuring insert

Since the maximum operating temperature influences the drift behavior, the temperature probe should be recalibrated or re-
placed at certain intervals to ensure reliable and precise temperature measurement.
The testing intervals are listed in the table below:

6.17 Intrinsic safety according to DIN EN 60079-11

v

Chapter 7 "ATEX"

Table 16: Testing intervals

Maximum operating temper-

ature

Pt - RTD temperature probes

Thermocouples

200 °C

5 years

5 years

550 °C

2 years

5 years

700 °C

1 year

2 years

1000 °C

Base metal 1 year

Noble metal 2 years

1500 °C

1 year

H

The testing intervals specified here are recommendations that must be adapted to the special conditions at the op-
erating location and,

if necessary, the user should perform the tests more regularly.