beautypg.com

2 analog inputs, 1 connection, Analog inputs – JUMO 14597 safetyM STB/STW Ex - Safety Temperature Limiter and Safety Temperature Monitor Operating Manual User Manual

Page 93: Connection, 8 configuration level

background image

8 Configuration level

87

2013-04-01

8.2

Analog inputs

k

Factory setting

8.2.1 Connection

Comment

Two sensors

This setting is provided for dual probes or for two different probes.
Each of the two analog inputs is monitored separately for a probe break or
probe short-circuit.

Single Pt100 in 2-wire circuit

V

Caution:
When only one probe (SIL2) is connected, the temperature limiter device is
reduced from

SIL3 to SIL2.

However, the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same sensor due to the simplified external wiring.

Single 4 to 20 mA

V

Caution:
When only one probe (SIL2) is connected, the temperature limiter device is
reduced from

SIL3 to SIL2.

However, the internal 2-channel structure (1oo2D) in the device still remains.
Both channels measure the same current signal due to the simplified external
wiring.