9 Technical data
110
9.11 Approvals/approval marks
9.12 Important information for the probes in Chapter 9.13 to Chapter 9.15
The following should be noted:
-
There is no safe isolation between the sensor and the fitting. As a result, the sensor connections are to be considered
grounded for the safety assessment.
-
Among other requirements, EN 60079-0 stipulates that for EPL Ga, the mass fraction of aluminum must be less than 10 %
for the production of metallic cases. The probe terminal head used by JUMO contains more than 10 % aluminum. There-
fore the terminal head must be secured with a suitable impact protection for the use of EPL Ga (zone 0). The impact protec-
Approval mark
Testing agen-
cy
Certificates/certification
numbers
Inspection basis
Valid for
DIN
DIN CERTCO
STB/STW 1228
DIN EN 14597
All device versions
SIL2, SIL3
TÜV
Nord
(German Tech-
nical Inspec-
tion Agency)
SAS-0190/2006-3, V2.0
DIN EN 61508
All device versions
PL e
DIN EN ISO 13849
All device versions
GL
Germanischer
Lloyd
36 790-11HH
All device versions
Pressure Equipment
Directive
TÜV Nord
(German Tech-
nical Inspec-
tion Agency)
07 202 4834 Z 5077/3/H
Pressure Equipment Di-
rective
97/23/EC
All device versions
ATEX
TÜV Nord
(German Tech-
nical Inspec-
tion Agency)
TÜV 11 ATEX 556139 X
Directive 94/9/EC
All device versions