Where to install the enclosure, Clearance requirements, Enclosure dimensions and weights – ETC Unison Auxiliary Enclosure Series User Manual

Page 9: N o t e

background image

1

Prepare for Installation

6

Where to Install the Enclosure

Unison auxiliary enclosures are designed to be surface mounted on load bearing walls in

an electrical closet or a room with restricted public access. It is recommended that you

install the enclosure at least 36" (914.4mm) off the floor surface.

Clearance Requirements

Enclosure Dimensions and Weights

N o t e :

Additional Unison DRd and auxiliary enclosures of the same size are the

exception to the 6" hinge side clearance rule. Unison enclosures are designed for

side by side use without issue.

Enclosure

Type

Height

Width

Depth

Product
Weight

a

a)Note: All weights are approximate.

Shipping

Weight

a

inches

mm

inches

mm

inches

mm

lbs

kgs

lbs

kgs

AX6 MCB
enclosure

21.8

553.7

13

330

8

203

27.6

12.5

35

16

AX12 MCB
enclosure

31

787

13

330

8

203

33

15

40

20

AX12X ML
enclosure

31

787

13

330

8

203

28

12.7

35

16

AX12X MCB
enclosure

31

787

13

330

8

20

33

15

40

20

12”

(305 mm)

6”

(152 mm)

17”

(432 mm)

36”

(914.4 mm)

Unison DRd enclosures require 12" (305mm) top clearance for proper

airflow through the cabinet. For sufficient door clearance, install the DRd

enclosure with at least 17" (432mm) of front clearance and 6" (152mm)

of clearance to the left of the door hinge from walls or other equipment.