Entering point calibration and alarm setpoints, Setting point update rates – Det-Tronics Mac - w/Supercard User Manual
Page 37

E
NTERING
P
OINT
C
ALIBRATION
AND
A
LARM
S
ETPOINTS
S
ETTING
P
OINT
U
PDATE
R
ATES
7. Enter the user-defined calibration value in the appropriate units.
See Units: under Device Information in the Point Configuration
screen for the proper units.
a. Select the “Calibration Range Now” box to display the
Calibration/Alarm Setting dialog box.
b. Enter the desired value and select Okay to accept the new value
or cancel to leave the current value unchanged.
8. Enter the user-defined Alarm 1 and 2 values. This defines what
levels will generate alarms.
a. Select the “Alarm 1 or Alarm 2 Now” box to display the
Calibration/Alarm Settings dialog box.
b. Enter the desired value and select Okay to accept the new value
or cancel to leave the current value unchanged.
Selecting the “Defaults” pushbutton will set the Calibration Range, Alarm
1, and Alarm 2 setpoints to their default values.
9.
Enter the desired point update rate in milliseconds.
a. Select the “Update Rate” button.
b. Enter the desired update rate in milliseconds. The minimum fre-
quency is 1000 ms (1 sec.) and the maximum is 10,000 ms (10
sec.). The default update is 5000 ms (5 sec.).
Holding down the ”option” key when selecting the update rate button will
allow the rate for all points to be changed simultaneously.
Point Configuration (
Á5)
2.24
95-8434
!
!