Pushbutton functions – Det-Tronics Mac - w/Supercard User Manual
Page 63

Not Communicating
The gateway has not been receiving the peri-
odic status updates from the target module.
Invalid Config.
Invalid configuration data has been received.
For a relay module, the most likely cause is
trying to download a configuration for anoth-
er type of device.
It is not possible for a device to receive invalid configuration data from
EagleVision, however it is possible for a third party Modbus RTU master
to write invalid data to a module through the gateway.
Goto Point
This button calls up a keypad allowing the
operator to go directly to any point on any of
the attached LON’s.
Next/Previous Point
These buttons allow the operator to view the
point displays for the next higher or lower
configured device connected to this gate-
way’s LON.
Inhibit
Select the Inhibit button to inhibit the current
point. When a point is inhibited, the gateway
relays will not respond to any events or
alarms generated by this module. Information
from this module will be displayed on the
screen and events configured in EagleVision
will respond.
Reset Relay
Click on the Reset Relay button to reset the
communication module’s relay.
Acknowledge
Select Acknowledge to acknowledge all
events and silence any audible annunciation.
Force Relay On
The relay is in a “force on” condition, caus-
ing it to be in its active state, regardless of
voting or other programmed responses.
Force Relay Off
The relay is in a “force off” condition, caus-
ing it to be in its inactive state, regardless of
voting or other programmed responses.
Relay Module Point Display
P
USHBUTTON
F
UNCTIONS
3.9
95-8434