The gateway has four relays, each of which can be configured to monitor
a contiguous group of points. In addition there is a gateway fault relay.
All relays can be configured to be energized or de-energized in normal
operation. Gateway relay operation is independent of the OIS.
1. Select Point Configuration from the Configure menu.
2. Select a point (1 through 4) and then select modify or double-
click on the desired gateway point.
Points 1 through 4 are always reserved for the gateways.
3. The Point Configuration screen for the gateway is displayed:
The Point Configuration screen provides an overview of the
gateway relay configuration:
Any alarm/fault item listed as True will energize/de-energize the
gateway relay when the alarm/fault condition is present.
Start Address
Displays the Modbus address where the start-
ing point number is stored.
End Address
Displays the Modbus address where the end
point number is stored.
Trigger Address Displays the Modbus address where the relay
trigger is stored.
Gateway Relay Configuration