beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System SAFETY MANUAL User Manual

Page 9

background image

5.1

95-8599

7

EQP Safety Device Diagnostics
The EQP Safety devices (EDIO/AIM/X3301/Eclipse)

automatically carry out a number of diagnostic checks

on a continuous basis. All checks are completed at

least once every two hours (diagnostic test interval).

Failure of any field device diagnostic will cause the

trouble relay on the Controller to open. It is the user’s

responsibility to determine what course of action is

appropriate for their situation when the Controller’s

trouble relay opens.

The internal diagnostic tests carried out by EQP Safety

devices are sufficient to meet the requirements for use in

a low demand SIL 2 safety function. Proof testing, which

is the responsibility of the user, is discussed in the “Proof

Testing” section of this manual.

X3301-SIL
The SIL EQP Model X3301 flame detectors are

configured with the use of S

3

software and the device

is safety rated at all available sensitivity settings. The

fire alarm status should be used as the safety input

signal for user logic. System “Proof Testing” should be

conducted after any change in configuration is made.

Note

Refer to the X3301 Safety Manual (number
95-8582) for specific requirements and
recommendations applicable to the proper
installation, operation, and maintenance of all
SIL-Certified X3301 IR flame detectors.

MODEL PIRECL-SIL
The SIL EQP Model PIRECL combustible gas detectors

are configured via S

3

software and the device is safety

rated. High and low alarm status should be used as the

safety input signal for user logic. The floating point gas

concentration value is available for information, but is not

safety rated and should not be used as part of the safety

function. System “Proof Testing” should be conducted

after any change in configuration is made.

Note

Refer to the Model PIReCL Safety Manual
(number 95-8630) for specific requirements
and recommendations applicable to the proper
installation, operation, and maintenance of all
SIL-Certified PIReCL IR gas detectors.

AIM-SIL ANALOg INPUT MODULE
The SIL AIM module is configured via S

3

software and

the device is safety rated. High and low alarm status

should be used as the safety input signal for user logic.

The SIL AIM module provides eight channels of

configurable analog input. The AIM Module is specially

designed to meet the requirements of IEC 61508 and

expands the input capability of the Det-Tronics Eagle

Quantum Premier System.

Each channel of the AIM safety module is an input that

can accept analog devices such as gas detectors. It is

the responsibility of the user to select suitable SIL rated

devices to connect to the AIM.

The EQP Controller continuously monitors the status of

the AIM. Input channels are supervised for out of range

signals.

Input Range and Configuration
The user shall enable out-of-range checking, with the

out-of-range low value configured to be at least 1mA,

and the out-of-range high value to be less than 24

mA and less than or equal to the connected device

maximum output minus safety accuracy.

All AIM channels intended for use must be configured

and downloaded from the EQP controller, otherwise they

will be ignored.

For complete information regarding system overview,

installation, operation, specifications, and configuration

of the AIM Analog Input Module, refer to the AIM Module

specification data sheet 90-1183 and/or the EQP

instruction manual number 95-8533.

EDIO-SIL ENhANCED DIgITAL INPUT/OUTPUT
MODULE
The SIL EDIO module provides eight channels of

configurable digital input or output. The EDIO Module

is specially designed to meet the requirements of IEC

61508 and expands the input and output capability

of the Det-Tronics Eagle Quantum Premier System.

The EQP Controller continuously monitors the status

of the EDIO and controls the outputs with EQPSL

communications.

Each channel of the EDIO safety module can be

configured as an input to accept fire detection devices

such as manual alarm stations, or as an output for

signaling or releasing. Both input and output circuits

can be configured for supervised (line monitoring) or

unsupervised operation. Channels are only SIL rated

when configured for the supervised mode of operation.

Unsupervised channels can be used for non-safety

related uses and are considered non-interfering. It is

the responsibility of the user to select suitable SIL rated

I/O devices to connect to the EDIO.