beautypg.com

Det-Tronics EQP Fire and Gas Detection/Releasing System SAFETY MANUAL User Manual

Page 13

background image

5.1

95-8599

11

X3301 MAgNETIC

Oi PROOf TEST

Tools Required:
• Magnetic oi test tool (part number 102740-002)

All flame detectors must be performance tested using

the Magnetic oi Procedure and inspected to ensure that

they are capable of providing expected performance

and protection. Note that the Magnetic oi Procedure

and Manual oi Tests are not interference free. During

these tests the unit is not performing normal flame

detection functions. Model X3301 provides an onboard

status LED, which indicates Green color when internal

operational parameters are normal. Upon successful

completion of the Magnetic oi test, the LED changes

to a Red color and an alarm status is sent to the EQP

controller. In the event the proof test is unsuccessful, the

LED remains Green and the controller does not indicate

a fire alarm.

PIRECL VISUAL fIELD INSPECTION PROOf TEST
Tools Required: None

Visual inspection of all Safety-Certified PIRECL Gas

Detectors shall be conducted weekly to confirm that no

external blockage of gas/vapor path into the sensing

chamber exists, e.g. debris, trash, snow, mud, external

equipment, etc. Corrective action shall include removal

of such impediments should they exist. All gas detectors

must be inspected to ensure that they are capable of

providing expected performance and protection. Model

PIRECL provides an onboard status LED that indicates

Green color upon inspection when internal operational

parameters are normal. Abnormal operating parameters

are indicated by Yellow color (Fault) or Red color (Alarm).

PIRECL gAS RESPONSE PROOf TEST
Tools Required:

Calibration Gas Kit (part number 006468-001)

available from Det-Tronics

This proof test, commonly referred to as a “gas bump

test”, requires application of high accuracy compressed

calibration gas to the detector while in NORMAL

operational mode and inspecting the signal output level

to ensure that the signal output is accurately indicative of

the applied test gas concentration.

When test gas is flowing into the detector, inspection

of proper gas response can be made by reading the

output displayed on the controller. Criteria for inspection

pass is a response signal within ±3% of applied gas

concentration (50% LEL test concentration applied).

If response test is not within acceptable limits, then a

Full Calibration procedure must be performed and Gas

Response Proof Test re-performed.

EQP USER LOgIC VERIfICATION
All user Safety Logic needs to be fully tested and

verified using the safety inputs and outputs. This is a

commissioning activity, however, if logic is modified

in the future, proof testing must be repeated. If the

Controller is replaced, project information must be

loaded into the new Controller and verified. The CRC

of project related data is calculated and saved by the

controller after each project download. The project CRC

can be viewed on the Controller’s display under User

Logic/General Info/Logic CRC. The project CRC should

be recorded and saved when proof testing is completed.

The project CRC from the Controller must be compared

to the saved value when a Controller is replaced to avoid

complete proof testing of the system.

INSTALLATION

General installation instructions are found in the

instruction manual for the EQP system, form number

95-8533.

Like other Det-Tronics EQP products, the ingress

protection rating of the EQP Safety Controller, EDIO,

and AIM is IP20. It will be necessary to mount the

EQP Safety Controller, EDIO, and AIM in a suitable

enclosure to provide mechanical and ingress protection

appropriate to the particular application. X3301 is IP66

minimum and PIRECL is IP67 minimum.

Access can be restricted by mounting the EQP

controller in a locked enclosure.

COMMISSIONINg PERSONNEL
The Safety Certified EQP System can be commissioned

by any qualified person with knowledge of EQP System

instruments and the configuration device being used.

SUITABLE APPLICATIONS

The EQP Safety System can be used to provide safety

functions up to Safety Integrity Level 2 (SIL 2). It can be

used in low demand applications only.

Typical low demand applications are:
• Fire and Gas protection systems, which monitor for the

presence of fire or a release of gas, and annunciate/

release when demanded upon.

In this case, the process safety time must be greater

than the response time of the EQP Safety System.